FS#13537 — pcc-165-n5
Incident Report for Network & Infrastructure
Resolved
The pcc-165-n5 went down (found switched-off)

Kernel uptime is 0 day(s), 0 hour(s), 8 minute(s), 57 second(s)

Last reset at 834566 usecs after Fri Jun 5 18:11:23 2015

Reason: Powered-down due to fan policy trigger
System version: 6.0(2)N2(2)
Service:

The \"reason\" is down to the fact the switch was off, but no logs before to alert us to a fan problem.

We will replace one of the 2 fans as a preventitive measure.

Update(s):

Date: 2015-06-08 08:11:49 UTC
Fan replaces as a preventitive measure.

2015 Jun 5 18:37:58.879 pcc-165-n5 %PFMA-2-PFMA_FAN_REMOVED: Fan module 2 N5548P-FAN removed
2015 Jun 5 18:37:59.021 pcc-165-n5 %NOHMS-2-NOHMS_ENV_ERR_FAN_DOWN: System minor alarm on fans: One fan missing or failed
2015 Jun 5 18:38:05.844 pcc-165-n5 %PFMA-5-PFMA_FAN_DETECT: Fan module 2 N5548P-FAN detected
2015 Jun 5 18:38:06.015 pcc-165-n5 %NOHMS-2-NOHMS_ENV_ERR_ALL_FAN_UP: Recovered: System minor alarm on fans: One fan missing or failed

Done.
Posted Jun 08, 2015 - 08:11 UTC