Get webhook notifications whenever Network & Infrastructure creates an incident, updates an incident, resolves an incident or changes a component status.
Eth1/31 vPC nodUpgrad trunk full 10G SFP-H10GB-C
Eth1/32 vPC nodUpgrad trunk full 10G SFP-H10GB-C
=> Ethernet1/32 is down (LC upgrade in progress)
Ongoing actions:
We are going to upate the 2nd n5 then reload the first n5.
The fex 100 and 101 will automatically switch to the 2nd n5 has it has already been updated.
The fex103->111 has will be reloaded and this will make the server unavailable during the time of reboot FEX.
Date: 2014-10-15 10:45:31 UTC 0% -- FAIL. Return code -1.
Remaining action::
\"Module(s) 103, 104, 105, 106, 107, 108, 109, 111 still need to be
upgraded\".
Install has failed. Return code 0x40930020 (Non-disruptive upgrade of
a module failed).
Please identify the cause of the failure, and try 'install all' again.
The ISSU on fex 102 is stuck.
and the 2nd N5 has just crashed with (same error)
Date: 2014-10-15 09:44:29 UTC Compatibility check is done:
Module bootable Impact Install-type Reason
------ -------- -------------- ------------ ------
1 yes non-disruptive reset
3 yes non-disruptive rolling
100 yes non-disruptive rolling
101 yes non-disruptive rolling
102 yes non-disruptive rolling
103 yes non-disruptive rolling
104 yes non-disruptive rolling
105 yes non-disruptive rolling
106 yes non-disruptive rolling
107 yes non-disruptive rolling
108 yes non-disruptive rolling
109 yes non-disruptive rolling
111 yes non-disruptive rolling