OVHcloud Network Status

Current status
Legend
  • Operational
  • Degraded performance
  • Partial Outage
  • Major Outage
  • Under maintenance
FS#8942 — UPS1 SBG
Scheduled Maintenance Report for Network & Infrastructure
Completed
During a UPS test before group test (http://status.ovh.net/?do=details&id=5005)
we have had a crashed card of the UPS 1. The UPS is now in bypass.

The manufacturer will intervene at the beginning of the night.


Update(s):

Date: 2013-07-10 01:17:16 UTC
During the last maintenances, the UPS was updated software-wise.
It turns out that the new software version rather bugged and leaves in some cases a light dysfunction between the network 1 and network 2 of the UPS.
This is what happened during the test.

The UPS has therefore just bypassed automatically thereafter the electrical shock but no card is crashed. The load didn't meet any of these events.

The technician will forward the information to the manufacturer.
And obviously, we have obliged a performing firmware (!!)
Posted Jul 10, 2013 - 01:11 UTC