FS#8809 — UPS 4
Scheduled Maintenance Report for Network & Infrastructure
Completed
The inverter is in bypass, the manufacturer will intervene on site at 19:00.

Update(s):

Date: 2013-06-13 22:22:57 UTC
Works are done, the inverter is performing.


Date: 2013-06-13 22:22:26 UTC
The incident was due to an infiltration in the outlet pipe of the hot air of the inverter. A manufacturing defect on one of the used pieces for a modernisation at the start of this week...
Few drops have caused an internal short circuit to the machine. The inverter has by-passed and the load didn't cutoff.

A team of the manufacturer is on site for preparations. Works should be accomplished before 01:00am.
Posted Jun 13, 2013 - 16:18 UTC