FS#4482 — UPS 7 in RBX2 and UPS 1 in RBX3
Incident Report for Network & Infrastructure
Resolved
Since yesterday we have minor alarms on the inverters:
\"The failure of one or more fans in the UPS has been detected \"

The manufacturer is on place to make the necessary changes.
The inverters will be by-passed during operations.



Update(s):

Date: 2010-09-09 08:37:06 UTC
The manufacturer will intervene again tomorrow to perform
the replacement of the second ventilator on UPS 1 to RBX3
and UPS 7 to RBX2.

The UPS will be by-passed during the operations.



Date: 2010-08-31 12:45:53 UTC
The manufacturer of the UPS is there to correct the problem.
The UPS will be bypassed during the changing of necessary parts.



Date: 2010-08-31 12:44:47 UTC
The manufacturer does not find the source of the problem.
He is working on it now and we are awaiting their solution ...

Inverters continue to have these minor alarms while the ventilation is working properly.
Posted Aug 31, 2010 - 12:43 UTC