OVHcloud Network Status

Current status
Legend
  • Operational
  • Degraded performance
  • Partial Outage
  • Major Outage
  • Under maintenance
FS#8429 — UPS 13 and 15
Scheduled Maintenance Report for Network & Infrastructure
Completed
Since 10:45pm, we have an increase in voltage supplied by EDF causing minor alarms on a cluster of UPS behind the transformer n°6.

Nothing serious. They receive 420V instead of 410V.
We will perform a re-adjustment of the transformer tomorrow morning.

Update(s):

Date: 2013-04-12 10:32:06 UTC
Settings are done.

End of work.

Date: 2013-04-12 06:48:43 UTC
The voltage level is normal since midnight.
We will proceed this morning to decrease setting TR6.
Posted Apr 12, 2013 - 01:40 UTC