FS#4495 — FS#8429 — UPS 13 and 15

Attached to Project— Datacenters
Maintenance
Roubaix 1
CLOSED
100%
Since 10:45pm, we have an increase in voltage supplied by EDF causing minor alarms on a cluster of UPS behind the transformer n°6.

Nothing serious. They receive 420V instead of 410V.
We will perform a re-adjustment of the transformer tomorrow morning.
Date:  Friday, 12 April 2013, 12:32PM
Reason for closing:  Done
Comment by OVH - Friday, 12 April 2013, 08:48AM

The voltage level is normal since midnight.
We will proceed this morning to decrease setting TR6.


Comment by OVH - Friday, 12 April 2013, 12:32PM

Settings are done.

End of work.