FS#404 — FS#4482 — UPS 7 a RBX2 et UPS 1 a RBX3
Attached to Project— Datacenters
Incident | |
Roubaix 2 | |
CLOSED | |
![]() |
Since yesterday, we have minors alarms on the inverters:
"The failure of one or more fans in the UPS has been detected "
The builder is on place to make necessary replacements.
The inverters will be by-passed during operations.
Date: Thursday, 02 September 2010, 10:34AM"The failure of one or more fans in the UPS has been detected "
The builder is on place to make necessary replacements.
The inverters will be by-passed during operations.
Reason for closing: Done
Additional comments about closing: The crashes were due to fans and due to control cards.
These parts were replaced and the uninterruptible power supplies were out to normal functioning.
The manufacturer did not find the problem's origin.
He is working on it actually and we are waiting the for the solution...
Inverters continue to have these minor alarms so that ventilation is working properly.
The manufacturer of the uninterruptible power supply is there to fix the problem.
The uninterruptible power supply will be by-passed during the changes of the necessary parts.