FS#7900 — Swtich to GE
Incident Report for Network & Infrastructure
Resolved
The datacenter has just switch to group generator.
We seek the origin of the problem.

Update(s):

Date: 2013-01-14 13:06:43 UTC
The return on EDF has been done, we reconnect in final and set up the fault report.

Date: 2013-01-14 13:05:45 UTC
The two 48V chargers that provide power supply to the 20 kV circuit breaker were still
in their temporary connection on the same 400V artery.

The upstream circuit breaker has blown for a reason not yet explained
Posted Jan 14, 2013 - 11:56 UTC