FS#3960 — FS#7900 — Swtich to GE

Attached to Project— Datacenters
Incident
Strasbourg 1
CLOSED
100%
The datacenter has just switch to group generator.
We seek the origin of the problem.
Date:  Monday, 14 January 2013, 14:06PM
Reason for closing:  Done
Comment by OVH - Monday, 14 January 2013, 14:05PM

The two 48V chargers that provide power supply to the 20 kV circuit breaker were still
in their temporary connection on the same 400V artery.

The upstream circuit breaker has blown for a reason not yet explained


Comment by OVH - Monday, 14 January 2013, 14:06PM

The return on EDF has been done, we reconnect in final and set up the fault report.