FS#3904 — FS#7845 — UPS 11

Attached to Project— Datacenters
Incident
Roubaix 1
CLOSED
100%
Following the crash on this UPS ( http://status.ovh.net/?do=details&id=3900 )
the manufacturer is on the spot and will bypass the device.
Date:  Tuesday, 08 January 2013, 19:57PM
Reason for closing:  Done
Comment by OVH - Thursday, 03 January 2013, 19:40PM

There is a transformer in an uninterruptible power supply. There was an electric arcing in the transformer and it is now in default.
Replacement of the transformer being particularly complicated and time consuming, we have decided to replace the entire UPS by one that we have in stock.

The operation will begin tomorrow, Friday morning at 5:00 am and will probably end on Saturday 12pm.


Comment by OVH - Monday, 07 January 2013, 09:31AM

The work hasn't been performed ​​Friday, we had to find another plan.
We start manipulations this morning.


Comment by OVH - Tuesday, 08 January 2013, 01:35AM

The room 9 has been switched temporarily to a generator (on hot).
The inverter 11 has been replaced and cabled this afternoon / night.
The manufacturer of the new inverter will be there at 08:00am, tomorrow morning to set the service.
We are keeping the room 9 tonight on the generator ( loaded to about 25% )


Comment by OVH - Tuesday, 08 January 2013, 19:55PM

We turned the UPS on and switched the room to the EDF network then moved to UPS mode.