Sep 27 13:47:11 GMT: %C6KENV-4-MINORTEMPALARM: module 1 asic-14
temperature crossed threshold #1(=110C). It has exceeded normal
operating temperature range.
Sep 27 13:47:43 GMT: %C6KENV-4-MINORTEMPALARM: module 1 asic-13
temperature crossed threshold #1(=110C). It has exceeded normal
operating temperature range.
Sep 27 13:50:52 GMT: %C6KENV-4-MINORTEMPALARM: EARL 1/0 outlet
temperature crossed threshold #1(=65C). It has exceeded normal operating
temperature range.
Sep 27 13:56:07 GMT: %C6KENV-4-MINORTEMPALARM: module 1 inlet
temperature crossed threshold #1(=60C). It has exceeded normal operating
temperature range.
Sep 27 13:58:45 GMT: %C6KENV-2-MAJORTEMPALARM: module 1 asic-14
temperature crossed threshold #2(=125C). It has exceeded allowed
operating temperature range.
Update(s):
Date: 2012-09-28 09:10:37 UTC For the moment the temperature is stable:
module 1 outlet temperature: 56C
module 1 inlet temperature: 36C
module 1 asic-13 temperature: 77C
module 1 asic-14 temperature: 78C
module 1 EARL outlet temperature: 44C
module 1 EARL inlet temperature: 30C
module 1 EARL device-2 temperature: 53C
module 1 XDB outlet temperature: 55C
module 1 XDB inlet temperature: 42C
Date: 2012-09-28 09:09:13 UTC We monitor the evolution of the temperature.
Date: 2012-09-27 16:28:11 UTC The currently is currently stable :
modul 1 outlet temperatur: 56C
modul 1 inlet temperatur: 36C
modul 1 asic-13 temperatur: 77C
modul 1 asic-14 temperatur: 78C
modul 1 EARL outlet temperatur: 44C
modul 1 EARL inlet temperatur: 30C
modul 1 EARL device-2 temperatur: 53C
modul 1 XDB outlet temperatur: 55C
modul 1 XDB inlet temperatur: 42C
Date: 2012-09-27 14:09:11 UTC We monitor the evolution of the temperature.
Date: 2012-09-27 14:08:36 UTC For the moment the temperature is back to normal:
bhs-s5-6k#sh env temperature
module 1 outlet temperature: 53C
module 1 inlet temperature: 36C
module 1 asic-13 temperature: 76C
module 1 asic-14 temperature: 78C
module 1 EARL outlet temperature: 42C
module 1 EARL inlet temperature: 29C
module 1 EARL device-2 temperature: 53C
module 1 XDB outlet temperature: 52C
Date: 2012-09-27 14:03:09 UTC We have replaced the FAN.