FS#7197 — Reboot hard room 2 (racks 02xxx)
Scheduled Maintenance Report for Bare Metal Cloud
Completed
We have several crashed reboot systems following a problem on the UPS 1 on Roubaix1:

http://status.ovh.co.uk/?do=details&id=3246

We are looking for the origin of the problem.

Update(s):

Date: 2012-08-28 08:58:10 UTC
As expected, the problem was solved with the inverter reparation.




Date: 2012-08-19 16:18:31 UTC
On UPS1, the outgoing tension of the phase 1 of UPS1 is always
167V which provokes the stopping of the ethernet cards
of the reboot systems.

The problem should be solved tonight with the rehabilitation of the UPS.