FS#3245 — FS#7197 — Reboot hard room 2 (racks 02xxx)

Attached to Project— Dedicated servers
Maintenance
RBX1
CLOSED
100%
We have several crashed reboot systems following a problem on the UPS 1 on Roubaix1:

http://status.ovh.co.uk/?do=details&id=3246

We are looking for the origin of the problem.
Date:  Tuesday, 28 August 2012, 10:58AM
Reason for closing:  Done
Comment by OVH - Sunday, 19 August 2012, 18:18PM

On UPS1, the outgoing tension of the phase 1 of UPS1 is always
167V which provokes the stopping of the ethernet cards
of the reboot systems.

The problem should be solved tonight with the rehabilitation of the UPS.


Comment by OVH - Tuesday, 28 August 2012, 10:58AM

As expected, the problem was solved with the inverter reparation.