FS#6564 — Beauharnois
Incident Report for Bare Metal Cloud
Resolved
Due to an electrical problem with Cologix Montréal, the link with the datacenter of Beauharnois is interrupted.

Update(s):

Date: 2012-04-10 13:35:21 UTC
We are going to intervene on the electrical supply of our trans equipment at Montreal in order to avoid new interruptions. the links to Beauharnois will be interrupted for a few minutes.

Date: 2012-04-10 07:07:37 UTC
We have had a cut off of the link between Montréal and Beauharnois between 05:37 and 05:52 GMT.



Date: 2012-04-08 22:43:41 UTC
Power was restored in both arrivals. The link is rising.

Note that we expect to eventually anyway to pass the network Canada / U.S. without going through Montreal to win in latency and avoid SPOF in Montreal.




Date: 2012-04-08 22:41:19 UTC
A fire alarm was triggered in Cologix. The UPC, which feeds one of our electric arrivals fell into the rack from our optical transmission equipment to Beauharnois. Unfortunately, we had problems with supply of power supplies of this equipment which can run on a power input and the same one that fell.

Power supplies are expected shortly. Electrical redundancy will be provided. We are also being put in service a second link fully independent. 2 ways to avoid this problem then. Unfortunately, none were still in place today ...



Date: 2012-04-08 22:32:04 UTC
An electric incident is confirmed on the site Canix C3 Montreal. Technicians are on their way. Further details to come.
Posted Apr 08, 2012 - 21:12 UTC