FS#6264 — UPS 12 RBX1
Incident Report for Network & Infrastructure
Resolved
The UPS bypassed only in the early afternoon.
We called the manufacturer's urgent service that moved quickly.

The fault detected is a leak on DC capacitors.
Works began about 1:30 earlier by the manufacturer assisted of our teams.
The inverter, which supplies rooms 12 and 14 (racks 12xxx and 14xxx) remains in bypass during the intervention.

The situation will get back to normal before 21h.

Update(s):

Date: 2012-01-16 09:22:16 UTC
The UPS has been put into ONLINE mode on Sunday night at 20:30.