Get webhook notifications whenever Network & Infrastructure creates an incident, updates an incident, resolves an incident or changes a component status.
Several customers raise the problem of
connection to Orange. This night we have
carried out the work of migration of th1 to
th2 and one of the two peering of Paris was
transferred to th2.
http://status.ovh.net/?do=details&id=1832
We look for the origin of the problem,it should not be a long way off
According to the graphs,the flow in a channel port
of 2x10G is not equal between the two 10G ports. We cut the port which we think is at the origin of the problem.
The overall flow port channel increased by 30%.
99% it is the port that poses the problem
If you do not have , or if you still have
the problem,would you send a confirmation email to noc@ovh.net, oles@ovh.net thank you in advance!
Update(s):
Date: 2011-10-01 18:47:44 UTC The problem is fixed.
Date: 2011-09-27 14:38:43 UTC We intervene on the physical interco.
Date: 2011-09-26 21:03:25 UTC Orange remounts us errors from their side on one of the two ports. We are forced to cut it at this time to avoid any impact on traffic. A technician will intervene tomorrow morning in order to fix the problem.
Date: 2011-09-26 21:00:42 UTC We checked totally the internal optical cabling for these two links, and replaced several garters.
We didn't note problems anymore. The two ports are properly balanced concerning traffic.
If you detect new inconveniences to Orange,please contact directly noc@ovh.net.
Date: 2011-09-26 15:29:58 UTC We checked another default on the optical link of the first port.
The 2 ports are currently down. The traffic is flowing via gsw.
Date: 2011-09-26 15:24:55 UTC Same problem. We're looking if it's possible to improve the
levels of attenutation on the link.
Date: 2011-09-26 15:23:31 UTC We changed the xenpack on the port 9/3. We try to reactivate the port.
Date: 2011-09-23 14:07:27 UTC A customer confirms the problem resolution.
Thank you for the feedback.