FS#1543 — FS#5532 — RBX1 / RBX3 : EDF network's instability

Attached to Project— Datacenters
Maintenance
All of the datacenters
CLOSED
100%
We had two short interruptions of EDF network this morning:
17-06-2011 6:31
17-06-2011 8:51

5 seconds each interruption.
No impact in the data center.

We contact EDF for information on the situation from their side.
Date:  Friday, 17 June 2011, 14:04PM
Reason for closing:  Done
Additional comments about closing:  No instability from EDF network side. The two cuts were invisible in the datacentre, invisible from the EDF side so we rather doubt the system of internal outage detection.